Page 1 of 11

Journal for Studies in Management and Planning

Available at http://edupediapublications.org/journals/index.php/JSMaP/

e-ISSN: 2395-0463

Volume 02 Issue 9

September 2016

Available online: http://edupediapublications.org/journals/index.php/JSMaP/ P a g e | 67

Grid Voltage Synchronization for Distributed

Generation Systems under Grid FaultConditions

Mr.V.BALU & RACHAKONDA CHANDRASHEKAR

Abstract—The actual grid code requirements for the grid

connection of distributed generation systems, mainly wind and

photovoltaic (PV) systems, are becoming very demanding. The

transmission system operators (TSOs) are especially concerned

about the low-voltage-ride-through requirements. Solutions based

on the installation of STATCOMs and dynamic voltage regulators

(DVRs), as well as on advanced control functionalities for the

existing power converters of distributed generation plants, have

contributed to enhance their response under faulty and distorted

scenarios and, hence, to fulfill these requirements. In order to

achieve satisfactory results with such systems, it is necessary to

count on accurate and fast grid voltage synchronization algo- rithms, which are able to work under unbalanced and distorted

conditions. This paper analyzes the synchronization capability of

three advanced synchronization systems: the decoupled double

synchronous reference frame phase-locked loop (PLL), the dual

second order generalized integrator PLL, and the three-phase

enhanced PLL, designed to work under such conditions. Although

other systems based on frequency-locked loops have also been

developed, PLLs have been chosen due to their link with dq0

controllers. In the following, the different algorithms will be pre- sented and discretized, and their performance will be tested in an

experimental setup controlled in order to evaluate their accuracy

and implementation features.

Index Terms—Electric variable measurements, electrical engi- neering, frequency estimation, frequency-locked loops, harmonic

analysis, monitoring, synchronization.

I. INTRODUCTION

THE power share of renewable energy-based generation

sys- tems is supposed to reach 20% by 2030, where wind and

photovoltaic (PV) systems are assumed to be the most outstand- ing examples of integration of such systems in the electrical

network.

The increased penetration of these technologies in the

electrical network has reinforced the already existing concern

among the transmission system operators (TSOs) about their

influence in the grid stability; as a consequence, the grid

connection standards are becoming more and more restrictive

for distribution generation systems in all countries

In the actual grid code requirements (GCRs), special con- straints for the operation of such plants under grid voltage fault

conditions have gained a great importance. These requirements

determine the fault boundaries among those through which a

grid-connected generation system shall remain connected to the

network, giving rise to specific voltage profiles that specify the

depth and clearance time of the voltage sags that they must

withstand. Such requirements are known as low voltage ride

through (LVRT) and are described by a voltage versus time

characteristic [7].

Although the LVRT requirements in the different standards

are very different, as shown in [8], the first issue that generation

systems must afford when a voltage sag occurs is the limitation

oftheirtransient response, in order to avoid its protective discon- nection from the network. This is the case, for instance, of fixed

speed wind turbines based on squirrel cage induction generators,

where the voltage drop in the stator windings can conduct the

generator to an overspeed tripping, as shown in [9]. Likewise,

variable speed wind power systems may lose controllability in

the injection of active/reactive power due to the disconnection

of the rotor side converter under such conditions [10], [11].

Likewise, PV systems would also be affected by the same lack

of current controllability.

Solutions based on the development of auxiliary systems,

such as STATCOMs and dynamic voltage regulators (DVRs),

have played a decisive role in enhancing the fault ride through

(FRT) capability of distributed generation systems, as demon- strated in [12]–[16]. Likewise, advanced control functionalities

for the power converters have also been proposed [17], [18].In

any case, a fast detection of the fault contributes to improving

the effects of these solutions; therefore, the synchronization

algorithms are crucial.

In certain countries, the TSOs also provide the active/reactive

power pattern to be injected into the network during a voltage

sag; this is the case for the German E-on [2] and the Spanish

Red Eléctrica Española (REE) [3]. Thistrend has been followed

by the rest of the TSOs; moreover, it is believed that this

operation requirement will be extended, and specific demands

for balanced and unbalanced sags will arise in the following

versions of the grid codes worldwide [19].

Regarding the operation of the distributed generation systems

under balanced and unbalanced fault conditions, relevant con- tributions, such as [20]–[29], can be found in the literature.

These solutions are based on advanced control systems that

need to have accurate information of the grid voltage variables

in order to work properly, something that has prompted the im- portance of grid synchronization algorithms. In power systems,

the synchronous reference frame PLL (SRF PLL) is the most

extended technique for synchronizing with three-phase systems

[30]. Nevertheless, despite the fact that the performance of SRF

PLL is satisfactory under balanced conditions, its response can

be inadequate under unbalanced, faulty, or distorted conditions

[31]–[33].

In this paper, three improved and advanced grid synchroniza- tion systems are studied and evaluated: the decoupled double

synchronous reference frame PLL (DDSRF PLL) [34], the dual

Page 2 of 11

Journal for Studies in Management and Planning

Available at http://edupediapublications.org/journals/index.php/JSMaP/

e-ISSN: 2395-0463

Volume 02 Issue 9

September 2016

Available online: http://edupediapublications.org/journals/index.php/JSMaP/ P a g e | 68

second order generalized integrator PLL (DSOGI PLL), [35]

and the three-phase enhanced PLL (3phEPLL) [36]. Their per- formance, computational cost, and reliability of the amplitude

and phase detection of the positive sequence of the voltage,

under unbalanced and distorted situations, have been evaluated

according to experimental grid fault patterns extracted from

[37] and [38], which have been reproduced in a real scaled

electrical network.

In the following sections, the discrete representation of each

PLL will be detailed (see Section IV), due to its great impor- tance in the final implementation of the control, after a brief

description of the different structures (see Section III). Finally,

their behavior will be tested in an experimental setup (see

Section VI), and their performance will be discussed, partic- ularly taking into account the accuracy of the positive-sequence

detection and their computational cost (see Section VII) when

considering different faulty scenarios, covering the response in

front of sags, frequency changes, and harmonic immunity.

II. GRID SYNCHRONIZATION SPECIFICATIONS

BASED ON GCR

Even though several works are published within the field of

grid synchronization, almost all of them are centered on ana- lyzing the individual dynamic performance of each proposal,

without first determining a time response window within the

dynamic behavior of the system under test, which would be

considered to be satisfactory.

In this paper, in order to evaluate the response of the grid

synchronization topologies under test, a common performance

requirement for all the structures has been established in this

section, considering the needs that can be derived from the

LVRT requirements.

Despite the fact that the detection of the fault can be carried

out with simpler algorithms, as shown in [39] and [40], the

importance of advanced grid synchronization systemsliesin the

necessity of having accurate information about the magnitude

and phase of the grid voltage during the fault, in order to inject

the reactive power required by the TSO.

In the German standard [2], it is stated that voltage control

must take place within 20 ms after the fault recognition, by

providing a reactive current on the low voltage side of the

Fig. 1. E-on voltage support requirement in the event of grid fault.

Fig. 2. REE voltage support requirement in the event of grid fault.

generator transformer to at least 2% of the rated current for each

percent of the voltage dip, as shown in Fig. 1. 100% reactive

power delivery must be possible, if necessary.

A similar condition is given in the Spanish grid code, where

the wind power plants are required to stop drawing inductive

reactive power within 100 ms of a voltage drop and be able to

inject full reactive power after 150 ms, as shown in Fig. 2.

Considering these demands, this paper will consider that the

estimation of the voltage conditions will be carried out within

20–25 ms, as this target permits it to fulfill the most restrictive

requirements, in terms of dynamical response, available in

the grid codes. This condition will be extended to frequency

estimation; although this parameter is more related to secondary

control algorithms than LVRT, the same time window between

20 and 25 ms will be considered in this work for the detection

of the disturbance.

III. DESCRIPTION OF THE THREE

SYNCHRONIZATION SYSTEMS

Many of the positive-sequence detection algorithms are

based on SRF PLLs [32]. Despite having a good response under

balanced conditions, their performance becomes insufficient in

unbalanced faulty grids (95% of cases), and their good opera- tion is highly conditioned to the frequency stability, which is

incompatible with the idea of a robust synchronization system.

Many authors have discussed different advanced models, which

Page 3 of 11

Journal for Studies in Management and Planning

Available at http://edupediapublications.org/journals/index.php/JSMaP/

e-ISSN: 2395-0463

Volume 02 Issue 9

September 2016

Available online: http://edupediapublications.org/journals/index.php/JSMaP/ P a g e | 69

abc

Fig. 3. DDSRF-PLL block diagram.

are able to overcome the problems of the classical PLL, using

frequency and amplitude adaptive structures which are able to

deal with unbalanced, faulty, and harmonic-polluted grids. In

the framework of these topologies, three PLL structures will be

discussed and evaluated in this paper.

A. DDSRF PLL

The DDSRF PLL, published in [34] and [41], was developed

for improving the conventional SRF PLL. This synchronization

system exploits two synchronous reference frames rotating at

Fig. 4. DSOGI-PLL block diagram.

as explained in [35]. The diagram of the DSOGI PLL is shown

in Fig. 4. As it can be noticed, the ISC method is implemented

by the positive-sequence calculation block.

To apply the ISC method, it is necessary to have a set of

signals, vα–vβ, representing the input voltage vector on the αβ

stationary reference frame together with another set of signals,

qvα–qvβ, which are in quadrature and lagged with respect

to vα–vβ. In the DSOGI PLL, the signals to be supplied to

the ISC method are obtained by using a dual second order

generalized integrator (DSOGI), which is an adaptive band- pass filter based on the generalized integrator concept [42].

At its output, the DSOGI provides four signals, namely, v

r

and v

r , which are filtered versions of vα and vβ, respectively, and qvr r

the fundamental utility frequency, one counterclockwise and ofv

r

α and qvβ

, which are the in-quadrature versions r

another one clockwise, in order to achieve an accurate detection

of the positive- and negative-sequence components of the grid

voltage vector when it is affected by unbalanced grid faults. The

diagram of the DDSRF PLL is shown in Fig. 3.

When the three-phase grid voltage is unbalanced, the funda- mental positive-sequence voltage vector appears as a dc voltage

on the dq+1 axes of the positive-sequence SRF and as ac

voltages at twice the fundamental utility frequency on the dq−1

axes of the negative-sequence SRF. In contrast, the negative- sequence voltage vector will cause a dc component on the

negative-sequence SRF and an ac oscillation on the positive- sequence SRF. Since the amplitude of the oscillation on the

positive-sequence SRF matches the dc level on the negative- sequence SRF and vice versa, a decoupling network is applied

to signals on the dq positive/negative SRF axes in order to

cancel out such ac oscillations. Low-pass filters (LPFs) in

Fig. 3 are responsible for extracting the dc component from

the signal on the decoupled SRF axes. These dc components

collect information about the amplitude and phase angle of the

positive- and negative-sequence components of the grid voltage

vector.

Finally, the PI controller of the DDSRF PLL works on the

decoupled q-axis signal of the positive-sequence SRF (v

∗ )

and performs the same function as in an SRF PLL, aligning the

α and vβ

.

A conventional SRF PLL is applied on the estimated

positive-sequence voltage vector, v

+ , to make this synchro- nization system frequency adaptive. In particular, the v

+ volt- age vector is translated to the rotating SRF, and the signal on

the q-axis, v

+

, is applied at the input of the loop controller.

As a consequence, the fundamental grid frequency (ωr

) and

the phase angle of the positive-sequence voltage vector (θ

+

t )

are estimated by this loop. The estimated frequency for the

fundamental grid component is fed back to adapt the center

frequency ωr of the DSOGI.

C. 3phEPLL

The enhanced phase-locked loop (EPLL) is a synchroniza- tion system that has proven to provide good results in single- phase synchronization systems [43]. An EPLL is essentially

an adaptive bandpass filter, which is able to adjust the cutoff

frequency as a function of the input signal. Its structure was

later adapted for the three-phase case [44], in order to detect

the positive-sequence vector of three-phase signals, obtaining

the 3phEPLL that is represented in Fig. 5.

In this case, each phase voltage is processed independently

by an EPLL. This block filters the input signal and generates

two sinusoidal outputs of the same amplitude and frequency, positive-sequence voltage with the d-axis. This signal is free of v

r r ◦ r

n and jvn

, the second one being 90 with respect to vn

.

ac components due to the effect of the decoupling networks; the

bandwidth ofthe loop controller can be consequently increased.

The resulting signals constitute the input for the computational

unit. Owing to these in-quadrature signals, the instantaneous

positive-sequence voltage component, v

+

, can be estimated

B. DSOGI PLL

The operating principle of the DSOGI PLL for estimating

the positive- and negative-sequence components of the grid

voltage vectors is based on using the instantaneous symmetrical

component (ISC) method on the αβ stationary reference frame,

by means of using the ISC method.

IV. DISCRETE IMPLEMENTATION

The performance ofthe differentstructures under test isreally

dependent on their final digital implementation, particularly on